4 devicenet option components – Yaskawa V1000 Option DeviceNet User Manual

Page 15

Advertising
background image

4 DeviceNet Option Components

YASKAWA ELECTRIC TOBP C730600 28B V1000 Option DeviceNet Installation Manual

15

Power-Up Diagnostics

An LED test is performed each time the drive is powered up. The initial boot sequence may

take several seconds. After the LEDs have completed

the DeviceNet diagnostic LED

sequence, the DeviceNet Option is successfully initialized. The LEDs then assume

operational conditions as shown in

Table 4

.

Table 5 Power-Up Diagnostic LED Sequence

NS

OFF

Offline or Power
supply OFF

Green

ON

Online
communications
established

Device is on-line and has connections in the established
state.

Green

Flashing

Online
communications not
established

Device is on-line but has no connections in the
established state.

Dup Mac-ID test has been passed, is on-line but has no
open connections to other nodes.

Red

ON

Communications
error

An error occurred that disables DeviceNet
communications.

• MAC ID duplication
• Bus Off detected

Red

Flashing

Communications
time-out

A communications time-out occurred with the master.

Green/
Red

Flashing

Communication
faulted

Specific communication faulted device.

• The device has detected a network access error and is in

the communications faulted state.

• The device has then received and accepted an Identify

communication fault request-long protocol message.

Sequence

Module Status (MS)

Network Status (NS)

Time (ms)

1

GREEN

OFF

250

2

RED

OFF

250

3

GREEN

GREEN

250

4

GREEN

RED

250

5

GREEN

OFF

-

Name

Indication

Operating Status

Remarks

Color

Status

Advertising