Installing the option unit, 5 installation procedure – Yaskawa V1000 Option DeviceNet User Manual

Page 20

Advertising
background image

5 Installation Procedure

20 YASKAWA

ELECTRIC

TOBP C730600 28B V1000 Option DeviceNet Installation Manual

Installing the Option Unit

Remove the front cover of the drive before installing the DeviceNet Option. Follow the

directions below for proper installation.

1.

Switch off the power supply to the drive.

DANGER! Electrical Shock Hazard - Do not connect or disconnect wiring while the power is on. Failure to

comply will result in death or serious injury. Before installing the DeviceNet Option, disconnect all power to

the drive. The internal capacitor remains charged even after the power supply is turned off. The charge

indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at

least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.

2.

Remove the front cover. The original drive front cover may be discarded because it

will be replaced by the DeviceNet Option cover in step 8.

Figure 2.5

Figure 6 Remove Front Cover

3.

Remove the bottom cover and connect the DeviceNet Option ground cable to the
ground terminal

.

Figure 2.6

Figure 7 Connect Ground Cable

Note: The four different ground cables packaged with the DeviceNet Option connect the unit to

different models. Select the proper ground cable from the DeviceNet Option kit depending on

drive size.

Ground terminal

Ground cable

Bottom cover

Advertising