5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 28B V1000 Option DeviceNet Installation Manual

23

Communication Cable Wiring

Procedure

Follow the instructions below to connect the communications cable to the terminal

block.

NOTICE: Tighten all terminal screws according to the specified tightening torque. Tightening screws too

tight could damage the terminal block, and leaving screws too loose can cause a short-circuit or drive

malfunction.

1.

Connect the communications cable to the terminal block as shown in the

diagram below.

Note: Communication lines should be separated from main circuit wiring and other electrical lines.

(Tightening torque: 0.5 to 0.6 (Nxm) or 4.4 to 5.3 (inch-lbs)) for Network Cable Wiring

Figure 2.11

Figure 13 Network

Cable Wiring

2.

Ensure all wiring connections are tightened and wire insulation is not

pinched in the terminal block. Remove any stray wire strands that touch

other terminals.

Terminal block

Preparing wire ends:

Screwdriver blade size

When not using
terminal extensions

About 5.5 mm

Up to
3.5 mm

Blade width

up to 0.6 mm

Pull back the shielding and lightly
twist the wire-end with fingers, to
keep the ends from fraying

DeviceNet comm cable

(Do not solder ends)

Loosen the screws and
insert the cable into the
opening on the terminal block

Black

Blue

White Red