YASKAWA ELECTRIC TOBP C730600 28B V1000 Option DeviceNet Installation Manual

6 DeviceNet Option Drive Parameters

6

DeviceNet Option Drive Parameters

Confirm proper setting of the all parameters in

Table 9

before starting network

communications.

Table 9 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

Frequency Reference
Selection

Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 or d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

(Set to 3

for DeviceNet)

b1-02

<1>

Run Command
Selection

Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS communications
3: Option PCB

1

(Set to 3

for DeviceNet)

F6-01

Operation Selection
after Communications
Error

Determines drive response when a bUS error is detected during
communications with the DeviceNet Option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-02

External Fault Detection
Conditions (EF0)

Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation

0

F6-03

Stopping Method for
External Fault from
Communication Option
Board

Determines drive response for external fault input (EF0) detection
during DeviceNet communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-07

<3>

NetRef/ComRef
Selection Function

0: Multi-step speed reference disabled
1: Multi-step speed reference allowed

1

F6-08

<3>

Reset Communication
Related Parameters

Determines if communication-related parameters F6-†† and F7-
†† are set back to original default values when the drive is
initialized using parameter A1-03.
0: Do not reset F6-†† and F7-†† parameters.
1: Reset F6-†† and F7-†† parameters.
Note: Setting this parameter does not affect communication-
related parameters.

0

F6-50

<4>

MAC ID

0~64

<5>

0

<5>