5 Mechanical Installation
5
Mechanical Installation
◆
Installation Environment
To help prolong the performance life of the drive, install the drive in an environment that is
within the specifications listed in
.
Table 5 Installation Environment
Environment
Conditions
Installation Area
Indoors
Ambient
Temperature
-10
°C to +40°C
Drive reliability improves in environments without wide temperature fluctuations.
Storage
Temperature
-20
°C to +60°C
Surrounding Area
Install the drive in an environment suitable for NEMA Type 4X, IP66 enclosures:
NEMA Type 4X – Enclosures constructed for either indoor or outdoor use to provide a
degree of protection to personnel against incidental contact with the enclosed equipment; to
provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust,
splashing water, hose-directed water, and corrosion; and that will be undamaged by the
external formation of ice on the enclosure.
IP66 – Dust-tight enclosures to do not allow any dust to penetrate. The enclosure guards the
drive against powerful jetting water sprayed from any direction and is protected against
access to hazardous parts with a wire.
Altitude
1000 m or lower
Vibration
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
2
Orientation
Install the drive vertically to maintain maximum cooling effects.