Fuse installation, 6 electrical installation, 1> single-phase drives do not have an l3 terminal – Yaskawa V1000 NEMA Type 4X/IP66 User Manual
Page 34: Drive

6 Electrical Installation
34
YASKAWA ELECTRIC TOBP C710606 35D YASKAWA AC Drive - V1000 NEMA Type 4X/IP66 Installation Manual
◆
Fuse Installation
For details on selecting the proper fuse, refer to the Quick Start Guide packaged with the
drive.
WARNING! Electrical Shock Hazard. Connect the recommended fuses between each input terminal and the
main circuit power supply (3-phase: L1, L2, L3, single-phase: L1, L2). Failure to use fuses in the power
supply could result in death or serious injury in the event of a short circuit inside the drive enclosure.
WARNING! Fire Hazard. Select the correct main circuit fuse for use with the drive. Failure to comply could
result in death or serious injury due to fire. Refer to the Quick Start Guide packaged with the drive to select
the correct main circuit fuse for UL/CE compliance.
Figure 13
Figure 13 Fuse Installation
<1> Single-phase drives do not have an L3 terminal.
M
1MCCB
MC
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Ground
L1
L2
L3
Three-phase
power supply
200 to 240 V
Drive
B1
+1
+2
B2
<1>