Wiring Preparation
1.
Refer to
Cable Gland Selection on page 36
to select the proper cable glands for
the drive.
2.
Prepare all cables with terminal ends to ensure proper connections.
3.
Remove the rubber bushing covering the conduit openings at the bottom of the
drive. Review
to route the main circuit and control circuit cables through
the proper conduit openings.
NOTICE: The rubber bushing used in the drive enclosure does not guarantee protection from water and
dust. The rubber bushings can be removed without the use of a tool. For more permanent installations,
replace rubber bushings with UL approved cable glands or gland cover plates with NEMA Type 4X, or IP66
integrity.
Figure 8
Figure 8 Conduit Openings
Control circuit cable
Power supply cable
Main circuit option cables
for connection of main circuit options
Motor cable