6 Electrical Installation

30

YASKAWA ELECTRIC TOBP C710606 35D YASKAWA AC Drive - V1000 NEMA Type 4X/IP66 Installation Manual

Wiring Preparation

1.

Refer to

Cable Gland Selection on page 36

to select the proper cable glands for

the drive.

2.

Prepare all cables with terminal ends to ensure proper connections.

3.

Remove the rubber bushing covering the conduit openings at the bottom of the
drive. Review

Figure 8

to route the main circuit and control circuit cables through

the proper conduit openings.

NOTICE: The rubber bushing used in the drive enclosure does not guarantee protection from water and

dust. The rubber bushings can be removed without the use of a tool. For more permanent installations,

replace rubber bushings with UL approved cable glands or gland cover plates with NEMA Type 4X, or IP66

integrity.

Figure 8

Figure 8 Conduit Openings

Control circuit cable

Power supply cable

Main circuit option cables
for connection of main circuit options

Motor cable