9 Drive Cooling Fans

50

YASKAWA ELECTRIC TOBP C710606 35D YASKAWA AC Drive - V1000 NEMA Type 4X/IP66 Installation Manual

Installing the External Fan

The external fan installation procedure differs by drive model. Refer to

Figure 22

to install

the external fan.

NOTICE: Install the fan so that the labeling faces inwards. The fan may be damaged if it is facing the wrong

direction.

Figure 22

Figure 22 Number of the External Fan and Conduit holes

1.

Place the rubber bushing for the fan into the heatsink holes.

NOTICE: Make sure all bushings fit securely into place. If the rubber bushing left loose, water and dust can

enter the drive.

2.

Feed the fan wiring through the rubber bushing.

3.

Plug the fan connector back in.

4.

Fill up the wiring hole in the rubber grommet to a minimum depth of 9.7 mm with
RTV sealant (KE-3494) specified in

Table 27

.

Figure 23

Figure 23 Fastening the Rubber bushing in 4A0038

5.

Install the fan guard onto the fan.

6.

Place the fan into its original position and fasten the fan into place.

A – Conduit hole

B – Fan unit

A – Tabs

B – Wiring hole filled with RTV sealant specified in

Table 27