6 Electrical Installation

32

YASKAWA ELECTRIC TOBP C710606 35D YASKAWA AC Drive - V1000 NEMA Type 4X/IP66 Installation Manual

Main Circuit and Control Circuit Wiring

NOTICE: Use only the recommended multi conductor cable and use only one cable per cable gland.

Attempting to pass more than one wire through a cable gland create a space between wires that reduces the

waterproofing and dustproofing capabilities of the cable gland, and may damage the drive.

NOTICE: Properly seal the rubber gasket along the outside of the cable gland. Improper seals may allow

water or oil into the drive and damage components.

Refer to the Electrical Installation chapter of the drive Quick Start Guide for proper main

circuit and control circuit wiring type, gauge, tightening torque and procedures.

Note: Use 3-wire cable for single phase input, and 4-wire cable for 3-phase input.

1.

After removing the rubber bushings, insert the cable glands into the holes and
tighten them with the locknut.

Refer to Cable Gland Selection on page 36

for the maximum allowable tightening

torque.

Figure 11

Figure 11 Inserting the Cable Glands

2.

Route the cables through the cable glands, following the instructions in

Cable

Gland Selection on page 36

.

Note: Use UL approved cable glands or gland cover plates with NEMA Type 4X, or IP66 integrity for

all drive conduit holes.

Figure 12

Figure 12 Cable Routing

Cable gland
(Locknut)

Cable gland
(Body)

Cable gland
(Locknut)

Cable gland
(Body)

Cable