9

3.2 Logical Analog Output (LAO) Summary

Point Description

Point #

GPD505

Parameter

GPD506/P5

Parameter

Units

(SI)

Slope Intercept

Default Min Max

Override

Time 20 n/a n/a

Hrs

1.0 0 8 1 12

Acceleration Time

31

n019

n018

Sec

0.1

0

10.0

0

3276.7

Deceleration Time

32

n020

n019

Sec

0.1

0

10.0

0

3276.7

Freq Command Upper

Limit

38 n030 n031 % 1.0 0 100 0 109

Freq Command Lower

Limit

39 n031 n032 % 1.0 0 0 0 100

Operational Mode

Select

55

n002

n002

-

1.0 0 6 0 8

Frequency Command

60

n/a

n/a

Hz

0.1

0

0

0

Note 1

PID Proportional Gain

63

n086

n086

-

0.1

0

1.0

0.0

10.0

PID Integral Time

64

n087

n087

Sec

0.1

0

10.0

0.0

100.0

PID Mode Select

65

n084

n084

-

1.0

0

0

0

3

Read Parameter

Number

70 n/a n/a -

1.0 0 0 1 114

Write Parameter

Number

72 n/a n/a -

1.0 0 0 1 114

Write Parameter Data

73

n/a

n/a

-

1.0

0

0

0

9999

Cable Loss Frequency

91

n/a

n/a

Hz

0.1

0

0

0

Note 1

Cable Loss Timeout

92

n/a

n/a

Sec

0.1

0

0

0

3276.7


Notes

1. Value dependent on maximum output frequency of the drive. Default is 60.0 Hz.

3.3 Logical Digital Input (LDI) Summary

Point Description

Point #

Off (0)

State

On (1)

State

Forward/Reverse Monitor

21

Forward

Reverse

Run/Stop Monitor

23

Stopped

Running

Drive Ready Monitor

35

Not Ready

Ready

Multifunction Output 1

40

Note 1

Note 1

Multifunction Output 2

41

Note 1

Note 1

Terminal S1 Monitor

42

Open

Closed

Terminal S2 Monitor

43

Open

Closed

Terminal S3 Monitor

44

Open

Closed

Terminal S4 Monitor

45

Open

Closed

Terminal S5 Monitor

46

Open

Closed

Terminal S6 Monitor

47

Open

Closed

Fault Monitor

93

Not Faulted

Faulted


Notes

1. States are dependent on the setup of the Multifunction Outputs. Refer to appropriate Technical

Manual.

3.4 Logical Digital Output (LDO) Summary

Point Description

Point #

Off (0)

State

On (1)

State

Default

Forward/Reverse

Command

22 Forward

Reverse Off

Run/Stop Command

24

Stop

Run

Off

Terminal S3 Command

25

Open ( See Note 1 )

Closed ( See Note 1 )

Off

Terminal S4 Command

26

Open ( See Note 1 )

Closed ( See Note 1 )

Off

Terminal S5 Command

27

Open ( See Note 1 )

Closed ( See Note 1 )

Off

Terminal S6 Command

28

Open ( See Note 1 )

Closed ( See Note 1 )

Off

Day/Night Mode Selection

29

Day Mode

Night Mode

Off

Advertising