3 drive monitoring, 1 operating status – Yaskawa GPD506/P5 with Apogee FLN Option User Manual

Page 17

Advertising
background image

16

4.3 Drive Monitoring

This section describes the logical points used to monitor the drive. Refer to the appropriate Technical
Manual for additional information.

4.3.1 Operating Status

The following table summarizes the input points available for monitoring the operating status of the drive.

Operating Variable

Point #

Description

Output Frequency

3

Reports output frequency in Hz.

Output Percentage

4

Reports operating output as a percentage of maximum output frequency.

Output Speed

5

Reports output speed in RPM (4-pole motor).

Output Current

6

Reports output current.

Output Power

8

Reports output power. This point is only available on GPD506/P5 drives.

Drive Temperature

9

Reports drive temperature. This point is only available on GPD506/P5 drives.

Kilowatt Hour Meter

10

Reports cumulative drive energy usage in kilowatts. This point is only available
on GPD506/P5 drives.

Megawatt Hour Meter

11

Reports cumulative drive energy usage in megawatts. This point is only
available on GPD506/P5 drives.

DC Bus Voltage

13

Reports DC bus voltage.

AC Output Voltage

14

Reports AC output voltage (i.e. voltage applied to motor).

Elapsed Timer – Hrs

15

Reports cumulative run time in hours.

Elapsed Timer – 10K Hrs

16

Reports cumulative run time in increments of 10K hours.

Fault Code

17

Reports drive fault status. This value is the decimal equivalent of a binary fault
word. It is the sum of the values associated with each fault bit, as listed below:

Fault

Bit Value

Overcurrent, Ground, Short Circuit

0

1

Overvoltage

1 2

Drive

Overload

2 4

Overheat

3 8

Main

Circuit

5 32

Brake

Transistor

6 64

External

7 128

Hardware

8 256

Motor

Overload

9 512

During Undervoltage

11

2048

Power Loss

12

4096

Phase

13

8192

Forward/Reverse Status

21

Reports the forward/reverse status (1=Reverse) as commanded from the source
selected by #55 (operator, terminal, or network). This allows the status to be
monitored even when the network is not the command source.

This value matches #22 only when the network is selected as the command
source (#55 = 6,7,8).

Run Status

23

Reports the run status (1=Run) as commanded from the source selected by #55
(operator, terminal, or network). This allows the status to be monitored even when
the network is not the command source.

This value matches #24 only when the network is selected as the command
source (#55 = 6,7,8).

Multifunction Output 1

25

Reports the status of Multifunction Output 1 (1=On). The function assigned to this
output is programmed in GPD505 parameter n040 or GPD506/P5 parameter
n041.

Multifunction Output 2

26

Reports the status of Multifunction Output 2 (1=On). The function assigned to this
output is programmed in GPD505 parameter n041 or GPD506/P5 parameter
n042.

Drive Ready Status

35

Reports whether or not the drive is ready to accept a run command (1=Ready).

Terminal S1 Monitor

42

Reports the status of Terminal S1 (1=Closed).

Terminal S2 Monitor

43

Reports the status of Terminal S2 (1=Closed).

Terminal S3 Monitor

44

Reports the status of Terminal S3 (1=Closed).

Terminal S4 Monitor

45

Reports the status of Terminal S4 (1=Closed).

Terminal S5 Monitor

46

Reports the status of Terminal S5 (1=Closed).

Terminal S6 Monitor

47

Reports the status of Terminal S6 (1=Closed).

Frequency Reference

61

Reports the frequency reference as commanded from the source selected by #55
(operator, terminal, or network). This allows frequency reference to be monitored

Advertising