Yaskawa GPD506/P5 with Apogee FLN Option User Manual
Page 18

17
Operating Variable
Point #
Description
even when the network is not the command source.
This value matches #60 only when the network is selected as the command
source (#55 = 4,5,6).
PID Feedback
62
Reports PID feedback. If PID is disabled, this value will be zero. This point is
only available on GPD506/P5 drives.
Fault Status
93
Reports the drive fault status (1=Fault).
4.3.2 Reading Other Parameters – #70, #71
Two points are defined for reading any drive parameter:
#70 - Specifies the parameter to be read.
#71 - Reports the value of the specified parameter.
Refer to the appropriate Technical Manual for a detailed description of all parameters.
NOTE: The increment listed in the Technical Manual must be considered when interpreting a
reported value. For example, a read of GPD506/P5 parameter n070 (GPD505 n066), DC
Injection Time at Stop, which reports 10 in #71 is actually a setting of 1, since the
increment for this parameter is 0.1 seconds.