4.5 Defining a New Slope & Intercept

Each analog point is defined with a default slope and intercept which scales data to its default units.
Often, a user may want to change these units to be consistent with the control variables of a system. A
common conversion for this drive is to convert frequency data points to a new reference unit.

Unit conversion is accomplished by “unbundling” a point and defining a new slope and intercept. The
following example illustrates how this is done:

1. A drive is installed in a pumping application and must maintain water pressure to a control point

defined in inches of water. The differential pressure sensor has a range of

± 2.5 inches of

water.


2. Frequency command (#60) controls the drive setpoint in hertz, with a default slope of 0.1 and

intercept of 0. The default range of this point is 0 – 60 hertz. An unbundled point can be
added with a slope and intercept defined to convert this range to

± 2.5 inches of water:

• The intercept of the unbundled point is the low end of the new range, or –2.5.

• The slope of the unbundled point is calculated as follows:


Using these values, the unbundled point can be commanded over the range of

±2.5, and the control

system will convert the values into the 0 – 60 hertz range for the drive.


Range)

(Current

Slope)

(Current

Range)

(New

Slope

New

×

=

0.008333

(60.0)

(0.1)

(5.0)

Slope

New

=

×

=