This point configures the drive as described below:

Point #

Point Description

GPD505

Parameter

GPD506/P5

Parameter

Units

(SI)

Slope Intercept Default Min

Max

55 Operational

Mode

Select

n002

n002

-

1.0 0 6 0 8

4.1.4 PID Configuration – #63, #64, #65

These points define the gains and mode of the PID controller. The PID modes selectable by #65 are
described below:

#65 PID

Mode

0 PID

Disabled

1 PID

Enabled

2

PI with Feed Forward

3 Inverted

PID



These points configure the drive as described below:

Point #

Point Description

GPD505

Parameter

GPD506/P5

Parameter

Units

(SI)

Slope Intercept Default Min

Max

63

PID Proportional Gain

n086

n086

-

0.1

0

1.0

0.0

10.0

64

PID Integral Time

n087

n087

Sec

0.1

0

10.0

0.0

100.0

65

PID Mode Select

n084

n084

-

1.0

0

0

0

3

4.1.5 General Purpose Setup – #72, #73

Two points are defined for setting any drive parameter:

#72 - Specifies the drive parameter to be set. Writing to this point initiates the write sequence.

#73 - Specifies the value to be written to the specified parameter. Writing to this point completes the

write sequence and causes the value to be sent to the drive.


Refer to the appropriate Technical Manual for a detailed description of all parameters.

NOTE: The increment listed in the Technical Manual must be considered when specifying a value.

For example, to set GPD506/P5 parameter n070 (GPD505 n066), DC Injection Time at Stop,
to 1 second,
#73 must be set to 10, since the increment for this parameter is 0.1 seconds.