Yaskawa GPD506/P5 with Apogee FLN Option User Manual

Page 12

Advertising
background image

11

Point #

Database

Descriptor

Point

Type

Units

(SI)

Slope

Interce

pt

On Text

Off Text

Default

{39}

FREQ LOW LM

LAO

PCT

1.0

0

--

--

0

{40}

MULTI OUT 1

LDI

--

--

--

ON

OFF

OFF

{41}

MULTI OUT 2

LDI

--

--

--

ON

OFF

OFF

{42}

TERM S1 MON

LDI

--

--

-

CLOSED

OPEN

OPEN

{43}

TERM S2 MON

LDI

--

--

-

CLOSED

OPEN

OPEN

{44}

TERM S3 MON

LDI

--

--

-

CLOSED

OPEN

OPEN

{45}

TERM S4 MON

LDI

--

--

-

CLOSED

OPEN

OPEN

{46}

TERM S5 MON

LDI

--

--

-

CLOSED

OPEN

OPEN

{47}

TERM S6 MON

LDI

--

--

-

CLOSED

OPEN

OPEN

{55}

OP MODE SEL

LAO

--

1.0

0

--

--

6

{60} FREQ

REF LAO HZ 0.1 0 -- -- 0

{61}

FREQ REF MON

LAI

HZ

0.1

0

--

--

0

{62} PID

FEEDBACK LAI HZ 0.1

0

--

--

0

{63} PI

GAIN LAO

-- 0.1 0 -- -- 1.0

{64} PI

TIME LAO

SEC

0.1

0 -- -- 10.0

(65} PID

SELECT LAO -- 1.0 0 --

--

0

{70}

RD PARAM NUM

LAO

--

1.0

0

--

--

0

{71}

RD PARAM DAT

LAI

--

1.0

0

--

--

0

{72}

WR PARAM NUM

LAO

--

1.0

0

--

--

0

{73}

WR PARAM DAT

LAO

--

1.0

0

--

--

0

{80}

S1 RUN ILOCK

LDO

--

1.0

0

ENABLE

DISABL

ENABLE

{81}

S5 AUTO RUN

LDO

--

1.0

0

ENABLE

DISABL

ENABLE

{90}

CBL LOSS FLT

LDO

--

1.0

0

ENABLE

DISABL

DISABL

{91}

CBL LOSS FRQ

LAO

HZ

0.1

0

--

--

0

{92}

CBL LOSS TMR

LAO

SEC

0.1

0

--

--

0

{93}

FAULT

LDI

--

--

--

FAULT

NO FLT

NO FLT

{94}

FAULT RESET

LDO

--

--

--

RST ON

RSTOFF

RSTOFF

{96}

EXTERNAL FLT

LDO

--

--

--

FLT ON

FLTOFF

FLTOFF



Notes

1. Slope is dependent on drive capacity. For drives with a rated current of 180 A or less, the slope is

0.1. For higher capacity drives, the slope is 1.0.