4.2 Drive Command and Control

This section describes the logical points used to command and control the drive. Refer to the appropriate
Technical Manual for additional information.

4.2.1 Forward/Reverse Command – #22

This point controls the Forward/Reverse command to the drive, as described below. The drive must be
configured for a network Forward/Reverse Command (#55 = 6,7,8) for this input to control the drive.

Point #

Point Description

Off (0)

State

On (1)

State

Default

22 Forward/Reverse

Command

Forward Reverse

Forward

4.2.2 Run/Stop Command – #24

This point controls the run/stop command to the drive, as described below. The drive must be configured
for a network Run/Stop Command (#55 = 6,7,8) for this input to control the drive.

Point #

Point Description

Off (0)

State

On (1)

State

Default

24 Run/Stop

Command

Stop

Run

Stop

4.2.3 Input Terminal Commands – #25, #26, #27, #28

These points control the multifunction terminal input commands, as described below. These commands
are equivalent to contact closures on external terminals S3 - S6, respectively. Function selection for
these inputs are configured in GPD505 parameters n036-n039 and GPD506/P5 parameters n037-n040.

Point #

Point Description

Off (0)

State

On (1)

State

Default

25

Terminal S3 Command

Depends on Terminal

S3 function selection

Depends on Terminal

S3 function selection

Off

26

Terminal S4 Command

Depends on Terminal

S4 function selection

Depends on Terminal

S4 function selection

Off

27

Terminal S5 Command

Depends on Terminal

S5 function selection

Depends on Terminal

S5 function selection

Off

28

Terminal S6 Command

Depends on Terminal

S6 function selection

Depends on Terminal

S6 function selection

Off

4.2.4 Frequency Command – #60

This point sets the frequency command of the drive, as described below. The drive must be configured
for a network Frequency Command (#55 = 4,5,6) for this input to control the drive.

Point #

Point Description

GPD505

Parameter

GPD506/P5

Parameter

Units

(SI)

Slope Intercept Default Min

Max

60 Frequency

Command n/a

n/a Hz 0.1

0

0

0 Note 1




Notes

1. Value dependent on maximum output frequency of the drive. Default is 60.0 Hz.