Installation 1-11

Option LEDs

The L

ON

W

ORKS

Option Unit is equipped with four indication LEDs for module and L

ON

W

ORKS

status indication. The LEDs are located on the

unit according to the figure below.



















Figure 1.7 – L

ON

W

ORKS

LED Locations

‹

Verify LonWorks Option Operation

„

Apply power to the drive.

„

Verify that the diagnostic LEDs on the front of the L

ON

W

ORKS

Option are in their correct state.

Table 1.3 – LED Status

LED Display

PWR Receive Transmit Fault

Service

Condition

Solution

BLINK

0.5Hz

Option is Not Configured

z

Configure Option

FLASH

1sON_2sOFF_ContON

Application missing

z

Download application image file

z

Assign network Identity

OFF

OFF

OFF

OFF

OFF

Power not supplied

z

Check that drive has power

z

Check option card seating in CN2 connector

ON BLINK BLINK

BLINK

OFF

Communications not

established

z

Check drive parameters (refer to table above)

z

Check connection between option and drive

ON

ON

OFF

Communications

Loss z

Check network cable connections

ON FLASH

OFF

OFF

Normal

communications

z

Flash each time serial task is complete

z

approximately 0.5Hz when drive is at STOP

z

approximately 1.0Hz when drive RUN is active

ON

FLASH

OFF

OFF

Normal

communications

z

Flash for every 5 network variables updates

„

Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the

drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.

„

Install the operator keypad and all drive covers.