Diagnostics 3-9

Cables and Wiring

Standard network wiring practices should be followed.

„

Do not route any network wires close to high voltage or high current wires. It is recommended that network wiring be in its own

conduit or trough. It may, however, be routed with low voltage DC wires.

„

If the network must cross high voltage or current wires, the network must cross perpendicular to the high voltage or current wires.

„

If a clean, noise free ground cannot be found locally to the device, route a ground wire of sufficient size to each device. Remember to

provide a single point ground to avoid ground loops.

„

Follow all local electrical codes.

‹

Network Cables

Choose the correct cable for the application and network configuration. For more information on cables and cabling refer to “Junction Box and

Wiring Guidelines for Twisted Pair L

ON

W

ORKS

Networks” Echelon engineering bulletin #005-0023-01. It may be downloaded from

www.echelon.com.

Table 3.3 BUS Topology Specifications

Cable

Maximum bus length(Meters)

Belden 85102

2700

Belden 8471

2700

Level IV, 22AWG

1400

JY(St) Y 2x2x0.8

900

TIA Category 5

900

Note: A doubly-terminated bus may have stubs of up to 3 meters from the bus to each device.

Table 3.4 Free Topology Specifications

Cable

Maximum device-to-device distance (Meters)

Maximum total Wire length(Meters)

Belden 85102

500

500

Belden 8471

400

500

Level IV, 22AWG

400

500

JY(St) Y 2x2x0.8

320

500

TIA Category 5

250

450

‹

Shield Grounds

Shields can be a prime source of noise in any network. The general rule is to ground the shield at the signal source. Depending on the type of
noise and the quality of the ground plane, it may be advisable to ground the shield at each device and/or at both ends of the network segment. If

there is noise on the network or intermittent short term communication failures, removing the shield from the device connection is usually one
of the first methods used restore communications stability. Also, if there is a disparity in the ground planes between devices, it is preferable to
disconnect the shield from the device connection. The shield must still remain contiguous even if removed from a device connector.

Table 3.5 – Shield Gournd

Device

Description

R

470k

Ω, 5%, ¼W

C1

0.1

μF, 10%, Metalized polyester, ≥100V








Figure 3.4 – L

ON

W

ORKS

Shield ground