Automatic restarts - nciautorstrt, Power loss ride-through – nciplridethru, Application overview 2-13 – Yaskawa LonWorks Option Card CM048 User Manual

Page 31

Advertising
background image

Application Overview 2-13

‹

Prohibit Frequencies - nciProFreq1, nciProFreq2, nciProFreqBW

These properties define bands of prohibited frequencies, selected to avoid certain areas of resonant motor vibration. Two separate bands can be
defined, with a common bandwidth. When this feature is selected, the motor is accelerated and decelerated through the prohibited areas. These

properties configure the drive as described below:

Table 2.14 - Prohibit Frequencies - nciProFreq1, nciProFreq2, nciProFreqBW

Property Name

Variable Type

Default

Parameter

Description

nciProFreq1

SNVT_freq_hz

0 Hz

d3-01

Sets the center frequency for the first band of prohibit frequencies.

nciProFreq2

SNVT_freq_hz

0 Hz

d3-02

Sets the center frequency for the second band of prohibit frequencies.

nciProFreqBW SNVT_freq_hz 1.0

Hz d3-04 Sets the bandwidth for prohibit frequencies.

‹

Automatic Restarts - nciAutoRstrt

This configuration property defines the number of automatic restarts that will be attempted under certain fault conditions.

Table 2.15 - Automatic Restarts - nciAutoRstrt

Property Name

Variable Type

Default

Parameter

Description

nciAutoRstrt SNVT_count 0

L5-01

Selects the number of times the drive attempts to automatically restart
after certain faults.

„

Restartable Faults

z

Overcurrent (oC)

z

Overvoltage (ou)

z

Undervoltage (Uu1)

z

Ground Fault (GF)

„

Non-Restartable Faults

z

Overload (oL_)

z

External (EF_)

z

Hardware (CPF_)

z

Fuse Blown (PUF)

z

Overcurrent (oC)

z

Overvoltage (oV) during deceleration

‹

Power Loss Ride-Through – nciPLRideThru

Table 2.16 - Drive Configuration Property - nciPLRideThru

Property Name

Variable Type

Default

Parameter

Description

nciPLRideThru

SNVT_count

0.1sec

L2-02

Sets the ride through time at momentary power loss

Table 2.17 - nciPLRideThru

nciPLRideThru

Value

Remarks

0 Disabled

Momentary

power

loss ride through is disabled

0.1 ~ 25.5sec

Enabled

The ride through time at momentary power loss *

* Parameter L2-01 must be set to 1 in order for this variable to be available. A setting of 0 or 2 in parameter L2-01 will disable power loss ride

through.