Vfd object configuration property summary, Application overview 2-7 – Yaskawa LonWorks Option Card CM048 User Manual

Page 25

Advertising
background image

Application Overview 2-7

‹

VFD Object Configuration Property Summary

Table 2.4 - VFD Object Configuration Property Summary

Property Name

Variable Type

Default

Parameter

Description

nciNmlSpeed

SNVT_rpm

1800 rpm

n/a

Configures nominal motor speed in rpm

nciNmlFreq SNVT_freq_hz

60Hz n/a

Configures nominal motor frequency in hertz All speed related data in percent are referenced
to this value

nciMinSpeed SNVT_lev_percent 0%

d2-02 Configures the minimum motor speed as a percentage of nciNmlFreq Sets the drive’s lower

limit for frequency commands

nciMaxSpeed SNVT_lev_percent 100%

d2-01 Configures the maximum motor speed as a percentage of nciNmlFreq Sets the drive’s upper

limit for frequency commands

nciRampUpTm SNVT_time_sec 10sec C1-01 Configures motor ramp up time from 0 to its operating setpoint Sets the drive’s output

acceleration rate

nciRampDownTm SNVT_time_sec 10sec

C1-02 Configures motor ramp down time from its operating setpoint to 0 Sets the drive’s output

deceleration rate

nciSndHrtBt SNVT_time_sec

0sec

(off) n/a Configures the maximum period of time that expires before automatic propagation of

nvoDrvCurnt nvoDrvSpeed nvoDrvVolt and nvoDrvPwr

nciRcvHrtBt SNVT_time_sec

0sec

(off) n/a Configures the maximum period of time that expires between network variable updates

before a cable loss condition is declared and the drive is stopped

nciMinOutTm SNVT_time_sec 1sec

n/a Configures the minimum period of time that expires before changes in output network

variables are propagated

nciLocation

SNVT_str_asc

All “\0”

n/a

Available for a description of the physical location of the node

nciDrvSpeedScale SNVT_lev_percent

100%

n/a

Scales the speed setpoint nviDrvSpeedStpt (saved configured value)

nciOpModeRun

SNVT_count

1

b1-02

Selects the source for start/stop and speed commands

nciDrvMaxFreq SNVT_freq_hz 60.0Hz E1-04 Reports

the maximum output frequency of the drive (read-only)

nciMtrFLA SNVT_amp *

E2-01

Sets the full load current rating of the motor

nciPLRideThru

SNVT_count

2.0sec

L2-02

Selects the drive’s response to momentary power loss ride through time

nciAutoRstrt

SNVT_count

0

L5-01

Selects the number of times the drive attempts to automatically restart after certain faults

nciProFreq1

SNVT_freq_hz

0Hz

d3-01

Sets the center frequency for the first band of prohibit frequencies

nciProFreq2

SNVT_freq_hz

0Hz

d3-02

Sets the center frequency for the second band of prohibit frequencies

nciProFreqBW SNVT_freq_hz 1.0Hz d3-04

Sets the bandwidth for prohibit frequencies

nciPIDSel

SNVT_count

0

b5-01

Selects the mode of the PID controller

nciPID_PGain SNVT_multiplier 20

b5-02 Sets

the proportional gain of the PID controller

nciPID_ITime SNVT_time_sec 5.0sec b5-03

Sets

the

integral time constant of the PID controller

nvoDrvRatedCur SNVT_amp

*

n9-01

Reports the output current rating of the drive (read-only)

nciStallLevAcc SNVT_count *

L3-02

Sets the stall level for output current during acceleration

nciStallLevRun SNVT_count *

L3-06

Sets the stall level for output current while at set speed

nciCblLossSpeed SNVT_lev_percent 0%

n/a

Sets

speed level commanded if network communication is lost

nciCblLossFltEna SNVT_switch Off

n/a Enables

an

EF0 fault to be declared if network communication is lost

nciOpModeFreqRef SNVT_count

1

b1-01 Selects frequency reference source

* - Value dependent on drive capacity. Refer to appropriate Parameter Access and/or Technical Manual.