Drive Command and Control

This section describes the network variables used to command and control the drive. Refer to the appropriate Technical Manual for additional
information.

‹

Run/Stop Command – nviDrvSpeedStpt

This network variable controls the run/stop command to the drive, as described below. The drive must be configured for a network Run/Stop

Command (nciOpModeRun = 2) for this input to control the drive.

Table 2.18 - Run/Stop Command – nviDrvSpeedStpt

nviDrvSpeedStpt

Run/Stop Command

State

Value

0 don’t

care

Stop

1 0

Run

1 >

0

Run

‹

Speed Setpoint - nviDrvSpeedStpt, nviDrvSpeedScale

These two network variables are used together with nciNmlFreq to control the speed setpoint, as follows:

Speed Setpoint = nciNmlFreq * nviDrvSpeedStpt.value * nviDrvSpeedScale

For example:

Table 2.19 - Speed Setpoint - nviDrvSpeedStpt, nviDrvSpeedScale

nciNmlFreq

nviDrvSpeedStpt.value

nviDrvSpeedScale

Frequency Setpoint

60 Hz

100%

100%

60 Hz

60 Hz

100%

75%

45 Hz

60 Hz

75%

50%

22.5 Hz

50 Hz

60%

35%

10.5 Hz

‹

Reverse Command - nviDrvSpeedScale

This network variable is used to reverse the direction of the motor. A negative value for nviSpeedScale will cause the motor to reverse direction.

‹

Fault / Fault Reset Control - nviOpCommands

Bit 0 of this network variable is used to command an external fault. Commanding this bit to a ‘1’ will fault the drive and bring it to a controlled
stop. ‘EF0’ is annunciated on the digital operator.

Bit 1 of this input variable is used to reset the fault state of the drive. If no fault conditions exist, the fault state of the drive will be reset
immediately upon receipt of this command. If fault conditions persist, the reset command remains latched until all fault conditions are cleared, at
which time the fault state is reset. The fault state of the drive may also be reset by issuing a RQ_CLEAR_ALARM mode request to the node.