Flue – MCZ Flair User Manual

Page 15

Advertising
background image

13

4-FLUE

Technical Dept. - All rights reserved - Reproduction is prohibited

EXTERNAL AIR INLET

It is mandatory to provide an adequate external air intake that supplies the combustion air required for the product to work properly. The

flow of air between the outside and the installation room may be direct, through an inlet in an external wall of the room; or indirect, via

air intake from adjoining rooms and connecting permanently with the installation room (see Figure 9 b). Adjoining areas may not include

sleeping areas, garages or general areas that present a fire hazard. During installation one must check the minimum clearances required

for air intake from outside. Take into account the presence of doors and windows that could interfere with the proper flow of air to the

stove (see diagram below).

The air intake must have a minimum total net area of 80 cm2: the surface must be increased accordingly if within the room there are other

active generators (for example: electric fan for stale air extraction, kitchen hood, other stoves, etc...), which could cause cause depression

in the room. One must verify that, with all the equipment on, the pressure drop between the room and the outside does not exceed a value

of 4 Pa. If necessary increase the intake section of the air inlet, which must be made at floor level and always protected with a bird-proof

outer protection grid and in such a way that it cannot be obstructed by any object.

It is possible to connect the air required for combustion directly to the outside air inlet, with a pipe of at least Ø50mm, with maximum

length of 3linear metres; each pipe bend shall be

considered equivalent to a linear metre. To attach the

pipe see the back of the stove.

For stoves installed in studio flats, bedrooms and

bathrooms (where allowed), it is mandatory to

connect the combustion air outside. In particular for

sealed stoves the connection must be sealed in order

not to compromise the overall sealed characteristic of

the system.

DISTANCE (metres)

The air inlet must be at a distance of:

1.5 m

UNDER

Windows, doors, smoke outlets, cavities, ....

1.5 m

HORIZONTALLY

Windows, doors, smoke outlets, cavities, ....

0.3 m

ABOVE

Windows, doors, smoke outlets, cavities, ....

1.5 m

AWAY

from smoke outlet

CONNECTION TO THE FLUE

The connection between the flue and the appliance must be via a smoke duct that complies with EN 1856-2. The connecting section must

extend no more than 4 m horizontally, with a minimum slope of 3% and with a maximum of 3 90% bends (accessible for inspection - do

not count the T fitting at the appliance outlet).

The diameter of the smoke duct must be equal to or greater than that of the appliance outlet (Ø 80 mm).

TYPE OF SYSTEM

SMOKE DUCT

Minimum vertical length

1.5 metres

Maximum length

(with 1 accessible 90° bend)

6.5 metres

Maximum length

(with 3 accessible 90° bends)

4.5 metres

Maximum number of accessible 90° bends

3

Horizontal sections

(minimum slope 3%)

4 metres

Use smoke ducts with a diameter of 80mm or 100mm depending on the type of system, with silicone gaskets or similar gaskets that

can withstand the high operating temperatures of the appliance (min. T200 class P1). The use of flexible metal hoses made of

fibre cement or aluminium is forbidden. For direction changes, we always recommend using a T fitting with an inspection

cap allowing easy access to clean the pipes. Always ensure that the inspection cap is put back in place and sealed hermetically with the

relevant seal intact after cleaning.

It is forbidden to connect several appliances to the same smoke duct, or the outlet from the overhead hoods. It is forbidden to extract the

combustion products directly through the wall, whether into indoor spaces or outdoors.

The smoke duct must be at a minimum distance of 400 mm from flammable or heat-sensitive structures.

Advertising
This manual is related to the following products: