Subaru Robin RGX3600 User Manual

Page 22

Advertising
background image

– 19 –

4-2 AC OUTPUT MEASURING

SWITCH

LOAD

TO AC RECEPTACLE

F

A

~

V

~

Use a circuit above for measuring AC output. A hot plate or lamp with a power factor of 1.0 may be used as a

load. Adjust the load and rpm, and check that the voltage range is as specified in the following table at the

rated amperage and rated rpm.

4-3 DC OUTPUT MEASURING

To DC Terminal

SW

Load

Measurement of DC output is executed with the switch turned ON while the current is regulated at 8.3A by

adjusting the load to the generator. If the voltage is within the range from 6V to 14V, the voltage output is

normal.

NOTE : If a battery is connected as a load to the generator, the DC output voltage will increase by

approximately 1 to 2 V.

Therefore, carefully observe the electrolyte level and do not overcharge the battery.

Model

Specification

50Hz-220V,230V

60Hz-120/240V

V

oltage range

RGX2900

RGX3600

RGX4800

226-259

113-130

207-238

50Hz-240V

226-259