4-4 MEASURING INSULATION RESISTANCE

Use a “Dr. Robin” generator tester in megger tester

mode or use a megger tester to check the insulation

resistance. Connect a megger tester to one of

receptacle output terminals and the ground terminal,

then measure the insulation resistance. An insulation

resistance of 1 megohm or more is normal. (The original

insulation resistance at the time of shipment from the

factory is 10 megohm or more.) If it is less than 1

megohm, disassemble the generator and measure the

insulation resistance of the stator, rotor and control

panel individually.

STATOR

Measure insulation resistance between each terminal

from the stator and the stator core.

Measured insulation resistance of 1M ohm or

more is normal.

If it is less than 1M ohm, leakage current and

electric shock might occur due to faulty insulation.

Replace with new one.

CONTROL PANEL

With AC circuit breaker turned on, measure insulation

resistance between each portion of electrical parts

and earth (grounding) terminal or control panel itself.

Measured insulation resistance of 1M ohm or

more is normal.

If it is less than 1M ohm, leakage current and electric

shock might occur due to faulty insulation.

Replace with new one.

Any part where the insulation resistance is less than 1M

has faulty insulation, and may cause electric leakage

and electric shock.

Replace the faulty part.