DISTRIBUTION TRANSFORMER MEASUREMENT

You can measure current, phase imbalance between phases, and true RMS neutral
current. True RMS measurement yields the effective value.

1) Set the rotary switch to " A ".
2) Clamp around a phase wire of the transformer. Be sure the jaws are completely

closed or measurement will not be accurate.

3) Observe the display for true RMS current.
4) Repeat your measurement for each phase to determine balance. Imbalanced

phases and/or harmonics can cause neutral currents.

5) Observe the display for true RMS current reading. If the phases are balance, any

significant current flow on the neutral may indicate the presence of harmonic cur

rents.

6) Press the HOLD/MAX

MINbutton to freeze the digital display.

7) Press and hold the SHIFTbutton (>I sec) to enter the PEAK mode (DH MAX dis

played). Measure the half cycle PEAK current. Divide first reading into the sec
ond reading to determine crest factor. Acrest factor other than 1.4 is an indication

of harmonic current.

8) Press and hold the SHIFT button (>11 sec) to exit the PEAK mode.
9) Press and hold the HOLD/MAX

MIN (> 1 sec) to enter dynamic recording

mode. Momentarily press HOLD/MAX

MIN button to review recorded maxi

mum, minimum, and average values.

10) Press and hold the HOLD/MAX

MIN button (> 1 sec) to exit recording.