Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual
Page 30
AMPROBE
DMIII MULTITEST
EN-28
6.3.2.
Faulty Cases
In the "
" mode, if a
Phase-to-Phase voltage
is lower than 100V, the
instrument displays the
screen to the right.
LOOP
05.06.01
-
- -
FRQ =60.0HZ V1-2=111V
V2-3= 0 V V3-1= 0V
LOW VOLTAGE T
PHASE ROTATION
Phase "T2 Voltage is lower
than 100V
In the "
" mode, if the
instrument detects two
phases
connected
together it displays the
screen to the right.
LOOP
05.06.01
-
- -
FRQ =60.0HZ V1-2=107V
V2-3= 0 V V3-1=107V
PHASE DOUBLED
PHASE ROTATION
Two phases are connected
together.
THE PREVIOUS RESULTS CANNOT BE SAVED.
In the
mode, if the
voltage of one or more
phase is too low, one or
more phases has a low
voltage the instrument
will
show
a
screen
similar to the along side
displayed.
LOOP
05.06.01
Phase
Sequence
not
correct
123
FRQ =60.0HZ V1-2=391V
V2-3= 0V V3-1= 0V
NOT CORRECT
Message “LOW Voltage
Phase T”: means that
Phase T has a low voltage
value. Similar message for