Amprobe, Technical specifications, Dmiii multitest – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual

Page 78: En-76

Advertising
background image

AMPROBE

DMIII MULTITEST

EN-76

14. TECHNICAL SPECIFICATIONS

14.1. TECHNICAL FEATURES

Accuracy is indicated as [% of reading + number of digits]. It refers to the following
atmospheric conditions: a temperature of 23°C ± 5°C with a relative humidity < 60%.

14.1.1. Safety Test functions

LOW

: 200mA CONTINUITY TEST (AUTO, RT+, RT- MODE)

Range [

]

Resolution [

]

Accuracy(*)

0.01

9.99

10.0

99.9

0.01

0.1

(2% Reading + 2 digit)

(*) After Test leads calibration
Test Current

> 200mA DC per R

5

(Test leads included)

Resolution for Test current:

1mA

Open Circuit Voltage

4V

V0

24V

INSULATION TEST

Test Voltage [V]

Range [M

]

Resolution [M

]

Accuracy

50

0.01

9.99

0.01

(2% Reading + 2 digit)

10.0

49.9

0.1

50.0

99.9

0.1

(5% Reading + 2 digit)

100

0.01

9.99

0.01

(2% Reading + 2 digit)

10.0

99.9

0.1

100.0

199.9

0.1

(5% Reading + 2 digit)

250

0.01

9.99

0.01

(2% Reading + 2 digit)

10.0

199.9

0.1

200

249

1

250

499

1

(5% Reading + 2 digit)

500

0.01

9.99

0.01

(2% Reading + 2 digit)

10.0

199.9

0.1

200

499

1

500

999

1

(5% Reading + 2 digit)

1000

0.01

9.99

0.01

(2% Reading + 2 digit)

10.0

199.9

0.1

200

999

1

1000

1999

1

(5% Reading + 2 digit)

Open circuit Test Voltage

<1.3 x Nominal Test Voltage

Short Circuit Current

<6.0mA with 500V Test Voltage

Nominal Test Current

500V

>2.2mA with 230k

other

>1mA with 1k

*Vnom

FREQUENCY MEASUREMENT

Range [Hz]

Resolution [Hz]

Accuracy

47.0

63.6

0.1

(0.1%Reading+1 digit)

RCD and LOOP function are active only for 50Hz

0,5Hz frequency

PHASE ROTATION : VOLTAGE MEASUREMENT

Range [V]

Resolution [V]

Accuracy

0

460V

1

(3%Reading + 2digit)

GROUND TEST: RESISTANCE MEASUREMENT WITH EARTH RODS

Range RE [

]

Resolution [

]

Accuracy

0.01

– 19.99

20.0

– 199.9

200 - 1999

0.01

0.1

1

(5% Reading + 3 digit)

Test Current

<10mA

– 77.5Hz

Open circuit Test Voltage

<20V RMS

GROUND TEST: RESISTIVITY MEASUREMENT

Range

Resolution

Accuracy

0.60

19.99

m

20.0

199.9

m

200

1999

m

2.00

99.99k

m

100.0

125.6k

m(*)

0.01

m

0.1

m

1

m

0.01 k

m

0.1 k

m

(5% Reading + 3 digit)

(*) setting distance = 10m
Test Current

<10mA

– 77.5Hz

Open circuit Test Voltage

<20V RMS


Advertising