Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual

Page 34

Advertising
background image

AMPROBE

DMIII MULTITEST

EN-32

6.4.2. Measurement procedure and results of "

" mode

1. Select

measurement mode by means of the F1 key.

2. Select the distance d between the earth rods by means the F3 and F4 keys.

The Distance measuring unit comply with Country setting (see par. 5.4).

3. Connect the 4 Black, Red, Blue and Yellow connectors of the single cables in the

corresponding input terminals of the instrument T1, T2, T3, T4.

d

d

d

d

T1 T2 T3 T4

I1 I2 I3

(V1) (V2) (V3)

( COM)

Instrument connection for Earth resistivity measurement

4. Press the START key. The instrument starts the test.

 At the end of the test

the instrument emits a
double

beep

indicating

that

the

test

is

correctly

terminated

and

displays the values to
the right.

EARTH

05.06.01

Ground

Resistivity

value

expressed in

m.

1.77

m

Vd= 1V

Test:04

AVG=0.74


DIST= 2m

Voltage value of electrical
noise

Number of Test

Average Value of Ground
Resistivity calculated over the
Number of Test displayed.

FUNC CLR

"

" Working mode

5. The instrument will show automatically the Average value of the Ground Resistivity

calculate over the tests performed. Press F2 to RESET this value and the number of
Test.

This result can be stored by pressing the SAVE key twice (refer to paragraph 9.1).


START

STOP

Advertising