"VOLTAGE" FUNCTION

This function permits to display in real time the RMS value of AC/DC voltage, the peak and
Thd values of the 3 phase voltages, the waveform and the harmonic spectrum of the 3
phase voltages.

7.4.1. Symbols
The VOLTAGE position has three working modes:

 METER
 WAVE
 HARM

These modes will be described in detail in the next paragraphs. The used symbols are
described below:

Symbol

Description

V1, V2, V3

RMS value of voltage (phase 1, phase 2, phase 3 respectively)

V12, V23 or V32,
V31

RMS value of phase to phase voltage

Vpk1, Vpk2, Vpk3,
Vpk12, Vpk32

peak value of voltage (phase 1, phase 2, phase 3 and phase-to-
phase voltage 12 and 32 respectively)

h01

h49

Harmonic 01

Harmonic 49

ThdV

Factor of total harmonic distortion of voltage

freq

Network frequency

Phseq

Phase sequence indicator

"123"

correct

"132"

inverted

"023"

null voltage on black wire

"103"

null voltage on red wire

"120"

null voltage on blue wire

"100"

null voltages on red and blue wires

"020"

null voltages on black and blue wires

"003"

null voltages on black and red wires

Tab. 1: Symbols used in VOLTAGE function