Amprobe – Amprobe DMIII-Multitest Power-Quality-Recorder User Manual

Page 36

Advertising
background image

AMPROBE

DMIII MULTITEST

EN-34

6.4.3. "2-W", "3-W" and "

" faulty cases

 If the instrument detects

the

External

Power

supply

adapter

connected to instrument
will show the message
displayed to the right.

EARTH

05.06.01

-

- -

Vd= ---V

Test:04

RAVG=0.74

REMOVE POWER


3-W

Disconnect the External
Power Supply Adapter

FUNC CLR

 If the Instrument detect

a voltage values higher
than 5V the instrument
will shows the screen
displayed to the right.

EARTH

05.06.01

Warning

symbol:

Voltage

noise in input.

-

- -

Vd= 230V

Test:04

RAVG=0.74

VOLT IN INPUT


3-W

FUNC CLR

 The

message

"Rc

high" indicates that the
instrument

can't

produce the minimum
current necessary for
measurement.

Check

that the terminals are
correctly

connected

and the Auxiliary earth
rod connected to T4
(yellow conductor) has
not been inserted in a
pebbly

or

poorly

conductive ground. If
necessary pour some
water around the rod.

EARTH

05.06.01

-

- -

Vd= 1V

Test:04

RAVG=0.74

Rc HIGH


3-W

Message

"Rc":

Check

Auxiliary Earth rods.

FUNC CLR