Amprobe A-5000 Sheath Fault Locator User Manual

Page 7

Advertising
background image

5

INtRodUCtIoN
The Amprobe AT-5000 Utility Locator with Sheath Fault Locating (SFL) option is designed to detect and pinpoint sheath and
other conductor faults that are in direct contact with the earth.
The AT-5000 with A-5000 (SFL) offers these unique features:

Fault level measurement at the transmitter

Simultaneous fault finding and line tracing

LCD bar graph representing the A-Frame signal strength for judging the proximity to faults, comparing multiple faults, and

detecting pinholes and “trees” in a power cable
Detection of low and high resistance faults

Automatic battery checking and low battery warning

Non-polarized A-Frame

Single-handed operation. No need to carry an R-5000 receiver as well as an A-frame during fault locating

Active SFL ohmmeter and voltmeter in the Transmitter

GENERAL INFoRmAtIoN ANd SAFEty
This manual contains basic advice for the installation and operation of Amprobe Utility Line and Sheath Fault Locators as well
as accompanying accessories. The manufacturer is not liable for damage to material or humans due to non-observance of the
instructions and safety advice provided in this manual. Therefore, this manual should be provided and reviewed by all personnel
associated with the line and sheath fault locating equipment.

Symbols used in this manual
Important instructions concerning the protection of staff and equipment as well as technical safety within this document are
labeled with one of the following symbols:

Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury or material
damage.

Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.

Notes have important information and useful tips on the operation of your equipment. Non-observance may result
in incorrect measurement results.

operating personnel
Amprobe utility line and sheath fault locators are intended for use by utility and contractor professionals.
Repair and maintenance
Repairs and service must only be done by Amprobe.

Safety Precautions
observed safety practices
Familiarize yourself with all required safety practices of the local utility company, or other owner of the plant before entering an
access area, or connecting an Amprobe transmitter.
Ensure that the line is de-energized and out of service, BEFORE connecting the transmitter directly to any conductor. NEVER
make a direct connection to a live power cable.
Follow the appropriate safety procedures to avoid the risk of injury if using a clamp on energized electrical or control lines.
Pay special attention when using a locator in high traffic areas.
Intended application
Safe operation is only realized when using the equipment for its intended purpose. Using the equipment for other purposes
may lead to human danger and equipment damage.
The limits described under the technical data section may not be exceeded.

A-5000 ShEAth FAULt LoCAtoR QUICk StARt GUIdE FoR thE ExPERIENCEd USER

Check Batteries Prior to Departing for the Field

1.

Check the battery level in the Transmitter, Receiver, and A-Frame by powering up each instrument.

Maximum use of the Transmitter’s SFL feature requires that the battery be fully-charged prior to field use. Amprobe
recommends charging the battery to full capacity before locating faults.

Replace/recharge if necessary. Turn the instruments OFF.
Ensure All Conductors Are De-Energized

2.

Lift Grounds

3.

Lift Grounds (of all conductors in the circuit) at both ends of the faulted cable section.

WARNING When the t-5000 transmitter is oN, the external oUtPUt JACk produces a high voltage. do not touch the jack!
Electrical shock will result!

Attach Transmitter to Conductor – Check Fault Resistance

4.

Make sure T-5000 transmitter is powered OFF.

1.