7.5

Ethernet Port Connection

7.5.1 Cable Specifications

The recommended cable is Category 5 or better. A Category 5 cable has four
twisted pairs of wires, which are color-coded and cannot be swapped. The
module uses only two of the four pairs.

The Ethernet port on the module is Auto-Sensing. A standard Ethernet straight-
through cable or a crossover cable can be used when connecting the module to
an Ethernet hub, a 10/100 Base-T Ethernet switch, or directly to a PC. The
module detects the cable type and uses the appropriate pins to send and receive
Ethernet signals.

Some hubs have one input that can accept either a straight-through or crossover
cable, depending on a switch position. In this case, ensure the switch position
and cable type agree.

Note: The standard connector view shown is color-coded for a straight-through cable.

Crossover cable

Straight- through cable

RJ-45 PIN

RJ-45 PIN

1 Rx+

3 Tx+

2 Rx-

6 Tx-

3 Tx+

1 Rx+

6 Tx-

2 Rx-

RJ-45 PIN

RJ-45 PIN

1 Rx+

1 Tx+

2 Rx-

2 Tx-

3 Tx+

3 Rx+

6 Tx-

6 Rx-

7.5.2 Ethernet Performance

Ethernet performance on the MVI69L-MBS module can affect the operation of
the application port in the following ways.
 Accessing the web interface (refreshing the page, downloading files, and so

on) may affect MBS performance

 High Ethernet traffic may impact MBS performance (consider using managed

switches to reduce traffic coming to module port).