– Read Holding Registers (4xxxx)

4

– Read Input Registers (3xxxx)

5

– Force (Write Single) Coil (0xxxx)

6

– Force (Write Single) Holding Register (4xxxx)

15

– Preset (Write) Multiple Coils (0xxxx)

16

– Preset (Write) Multiple Registers (4xxxx)

MB Address in
Device

0 to 9999

Specifies the register or digital point address offset within
the Modbus slave device. The MBS Master reads or writes
from/to this address within the slave.

Refer to the documentation of each Modbus slave device for
their register and digital point address assignments.

Note: The value entered here does not need to include the
“Modbus Prefix” addressing scheme. Also, this value is an
offset of the zero-based Modbus addressing scheme.

Example: Using a Modbus Function Code 3 to read from
address 40010 in the slave, a value of ‘9’ would be entered
in this parameter.

The firmware (internally) adds a ‘40001’

offset to the value entered. This is the same for all Modbus
addresses (0x, 1x, 3x, 4x).

Override Value
Upon Error

This parameter is only applicable for Enable Codes 3
(Bit/Word Override) or 4 (Float Override).
If an error occurs associated to a read command the module
automatically populates the associated database area with
this override value.