MVI69L-MBS ♦ CompactLogix Platform

Using Controller Tags

Communication Module

User Manual

ProSoft Technology, Inc.

Page 85 of 154

January 6, 2014

5.4.3.5 MBS.CONTROL.SlavePoll

This array allows the processor to enable, disable and retrieve status for slaves.

Tag Name

Range

Description

MBS.CONTROL.SlavePoll.
Port1

-

Port 1 slave polling control array

MBS.CONTROL.SlavePoll.
Port1.EnableSlaves

0 or 1

Slave Poll request
0 = Disable, 1 = Enable

MBS.CONTROL.SlavePoll.
Port1.EnableSlaveCount

1 to 60

Number of slaves to be enabled

MBS.CONTROL.SlavePoll.
Port1.EnableSlavesIDs[x]

-

Data array associated to enable slave request
where word x corresponds to slave ID x (0-based).
1 = Enable slave

MBS.CONTROL.SlavePoll.
Port1.DisableSlaves

0 or 1

Triggers disable slaves request
0 = Disable, 1 = Enable

MBS.CONTROL.SlavePoll.
Port1.DisableSlaveCount

1 to 60

Number of slaves to be disabled

MBS.CONTROL.SlavePoll.
Port1.DisableSlavesIDs[x]

-

Data array associated to disable slave request
where word x corresponds to slave ID x (0-based).
1 = Disable slave

MBS.CONTROL.SlavePoll.
Port1.GetSlavesStatus

0 or 1

Triggers request to read slave status
0 = Disable, 1 = Enabled

MBS.CONTROL.SlavePoll.
Port1.SlavesStatus[x]

-

Data array with status

5.4.3.6 MBS.CONTROL.Time

This array allows the processor to get or set module time.

Tag Name

Range

Description

MBS.CONTROL.Time.SetTime

0 or 1

Sends the PLC time to the module
0 = Disable, 1 = Enable

MBS.CONTROL.Time.GetTime

0 or 1

Retrieves the time from the module to PLC
0 = Disable, 1 = Enable

MBS.CONTROL.Time.Year

0 to 9999

Four digit year value. Example: 2014

MBS.CONTROL.Time.Month

1 to 12

Month

MBS.CONTROL.Time.Day

1 to 31

Day

MBS.CONTROL.Time.Hour

0 to 23

Hour

MBS.CONTROL.Time.Minute

0 to 59

Minute

MBS.CONTROL.Time.Second

0 to 59

Second

MBS.CONTROL.Time.Milliseconds

0 to 999

Millisecond