MVI69E-MBS ♦ CompactLogix Platform

Diagnostics and Troubleshooting

Communication Module

User Manual

ProSoft Technology, Inc.

Page 101 of 162

January 6, 2014

4 In the Connection Setup dialog box, click B

ROWSE

D

EVICE

(

S

)

to start ProSoft

Discovery Service. Right-click the module and choose A

SSIGN

T

EMPORARY

IP.

5

The module’s default IP address is usually 192.168.0.250. Choose an unused
IP within your subnet, and then click OK.









Important: The temporary IP address is only valid until the next time the module is initialized. For

information on how to set the module’s permanent IP address, see Ethernet 1 on page 61.

6 Close the ProSoft Discovery Service window. Enter the temporary IP address

in the Ethernet address field of the Connection Setup dialog box, then click
T

EST

C

ONNECTION

to verify that the module is accessible with the current

settings.


7 If the Test Connection is successful, click C

ONNECT

. The Diagnostics window

is now accessible.