MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform

Reference

Distributed Network Protocol Interface Module

Page 74 of 119

ProSoft Technology, Inc.

November 3, 2008

Block Format for Write

Word Offset in
Block

Data Field(s)

Description

0 Block

ID This field contains the value of 9958 identifying

the event block to the module.

1 Event

Count

This field contains the number of events
contained in the block. Valid values for this field
are 1 to 11.

2 Sequence

Counter

This field holds the sequence counter for each
9958 block transfer. This synchronizes and
confirms receipt of the block by the module.

3

DNP Binary Input Data
point

This is the data point in the DNP binary input
database represented by the event.

4 Month/Day/State

Formatted: bits 0 to 4 = Day, bits 8 to 11 =
Month, bit 15 = digital state for point. All other
bits are ignored.

5 Hour/Minute

Formatted: bits 0 to 5 = Minutes, bits 8 to 12 =
Hour. All other bits are ignored.

6 Sec/Millisecond

Formatted: bits 0 to 9 = Milliseconds, bits 10 to
15 = Seconds.

7

Year

This is the four digit year for the event.

8 to 12

Five words of data for Event #2.

13 to 17

Five words of data for Event #3.

18 to 22

Five words of data for Event #4.

23 to 27

Five words of data for Event #5.

28 to 32

Five words of data for Event #6.

33 to 37

Five words of data for Event #7.

38 to 42

Five words of data for Event #8.

43 to 47

Five words of data for Event #9.

48 to 52

Five words of data for Event #10.

53 to 57

Five words of data for Event #11.

58 to n

Spare

Not Used

To ensure the receipt of this block of information, the module returns a block
9958 with the sequence counter set to the value of the last successful block 9958
received.

Block Format for Read

Word Offset in
Block

Data Field(s)

Description

0

Block ID

Identification code for block set to 9958.

1 Block

ID Block identification code for request from PLC by

the module.

2 Event

Count

This field contains the number of events
processed by the module.

3 Sequence

Counter

This field contains the sequence counter of the
last successful block 9958 received.

4 to n

Spare

Not used