ProSoft Technology MVI69-DNPSNET User Manual

Page 85

Advertising
background image

Reference MVI69-DNPSNET

♦ CompactLogix or MicroLogix Platform

Distributed Network Protocol Interface Module

ProSoft Technology, Inc.

Page 85 of 119

November 3, 2008

DNP Digital Output Data

This data type stores digital control and command state data received from the
DNP master unit with a value of 1 or 0. The size of this data area is determined
from the configuration parameter Binary Outputs (defines number of words, each
containing 16 binary output points). These data are transferred from the module
to the PLC using the write operation. Therefore, these data are read-only for the
PLC, as the PLC cannot directly alter these values in module. It is the
responsibility of the DNP master unit to maintain this data. For example, if the
DNP master sets a digital point on, it will remain on until the master resets the
point. A data flow diagram for the digital output data is shown in the following
figure.

Advertising
This manual is related to the following products: