Start here, System requirements, Ge 9) – ProSoft Technology MVI69-DNPSNET User Manual

Page 9: 1 start here

Advertising
background image

Start Here

MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform

Distributed Network Protocol Interface Module

ProSoft Technology, Inc.

Page 9 of 119

November 3, 2008

1 Start

Here

In This Chapter

™ System

Requirements ............................................................................. 9

™ Package

Contents ................................................................................. 10

™ Install ProSoft Configuration Builder Software....................................... 11

™ Setting

Jumpers .................................................................................... 12

™ Install the Module in the Rack ............................................................... 13

™ Connect your PC to the Processor ........................................................ 16

™ Download the Sample Program to the Processor.................................. 17

™ Connect your PC to the Module ............................................................ 20

Installing the MVI69-DNPSNET module requires a reasonable working
knowledge of the Rockwell Automation hardware, the MVI69-DNPSNET Module
and the application in which they will be used.

Caution: It is important that those responsible for implementation can complete the

application without exposing personnel, or equipment, to unsafe or inappropriate working
conditions. Safety, quality and experience are key factors in a successful installation.

1.1 System

Requirements

The MVI69-DNPSNET module requires the following minimum hardware and
software components:

ƒ Rockwell Automation CompactLogix or MicroLogix processor, with

compatible power supply and one free slot in the rack, for the MVI69-
DNPSNET module. The module requires 800mA of available power.

Important: The MVI69-DNPSNET module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus).
Important: For 1769-L23x processors, please make note of the following limitations.
ƒ

1769-L23-QBFC1B = 800mA at 5Vdc (1 MVI69-DNPSNET will use all 800mA of available
power. No other modules can be used with an MVI69 module connected to this processor).

ƒ

1769-L23E-QB1B = 1000mA at 5Vdc (1 MVI69-DNPSNET will use 800mA of available power.
One other module can be used on this rack provided it consumes less than 200mA at 5Vdc.

ƒ

1769-L23E-QBFC1B = 450mA at 5Vdc (no MVI69 module can be used with this processor)

ƒ Rockwell Automation RSLogix 5000 (CompactLogix) or RSLogix 500

(MicroLogix) programming software

ƒ Rockwell Automation RSLinx communication software

Advertising
This manual is related to the following products: