ProSoft Technology MVI69-DNPSNET User Manual

Page 75

Advertising
background image

Reference MVI69-DNPSNET

♦ CompactLogix or MicroLogix Platform

Distributed Network Protocol Interface Module

ProSoft Technology, Inc.

Page 75 of 119

November 3, 2008

Block 9959 - Processor Analog Input Event

If the processor sends a block 9959, the module will place the analog input event
data in the block into the event buffer and alter the data values for the points in
the DNP analog input database. The format for the event message is shown in
the following table.

Block Format for Write

Word Offset in Block

Data Field(s)

Description

0 Block

ID

This field contains the value of 9959 identifying
the event block to the module.

1 Event

Count

This field contains the number of events
contained in the block. Valid values for this field
are 1 to 9.

2 Sequence

Counter

This field holds the sequence counter for each
9959 block transfer. This synchronizes and
confirms receipt of the block by the module.

3

DNP Analog Input
Data point

This is the data point in the DNP analog input
database represented by the event.

4

Analog Input Value

This is the new analog input value represented in
the event.

5 Month/Day

Formatted: bits 0 to 4 = Day, bits 8 to 11 =
Month. All other bits are ignored.

6 Hour/Minute

Formatted: bits 0 to 5 = Minutes, bits 8 to 12 =
Hour. All other bits are ignored.

7 Sec/Millisecond

Formatted: bits 0 to 9 = Milliseconds, bits 10 to
15 = Seconds.

8

Year

Four digit year value for event.

9 to 14

Six words of data for Event #2.

15 to 20

Six words of data for Event #3.

21 to 26

Six words of data for Event #4.

27 to 32

Six words of data for Event #5.

33 to 38

Six words of data for Event #6.

39 to 44

Six words of data for Event #7.

45 to 50

Six words of data for Event #8.

51 to 56

Six words of data for Event #9.

57 to n

Spare

Not Used

To ensure the receipt of this block of information, the module returns a block
9959 with the sequence counter set to the value of the last successful block 9959
received.

Block Format for Read

Word Offset in Block

Data Field(s)

Description

0

Block ID

Identification code for block set to 9959.

1 Block

ID

Block identification code for request from PLC by
the module.

2 Event

Count

This field contains the number of events
processed by the module.

Advertising