5.2 Tuning-less Function

5-15

5

Adjustments

4.

For 3rd digit, select one of the load levels in the

Tuning-less Load Level

list.

• If the response waveform results in overshooting or if the load moment of inertia exceeds the allowable

level, select

2: Tuning-less Load Level 2

. (If any damage caused when the load moment of inertia

exceeds the allowable level, these conditions are regarded as being outside the scope of the warranty.)

• If a high-frequency noise is heard, select

0: Tuning-less Load Level 0

.

5.

For 2nd digit, select one of the tuning-less levels in the

Tuning-less Level

list.

The higher the value of the level is, the higher the gain will be. A higher gain means better response.

Note 1. If the tuning-less level is too high, vibration might occur. Lower the level if vibration occurs.

2. If the tuning-less level is changed, the automatically set notch filter will be canceled (disabled). If any

vibration occurs, the notch filter will automatically be set again.

6.

Click

OK

.

7.

To enable the change in the setting, restart the SERVOPACK.