Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. o • 1/13

Figure 7.3

Top Vent - Horizontal Termination

Venting with 1 elbow

H

1

V

1

V Minimum

H

1

Maximum

90 Elbow

1-1/2 ft. (457 mm)

1 ft. (305 mm)

3 ft. (914 mm)

1-1/2 ft. (457 mm)

3-1/2 ft. (1067 mm)

2 ft. (610 mm)

5 ft. (1.52 m)

2.5 ft. (762 mm)

6 ft. (1.85 m)

3 ft. (914 mm)

7 ft. (2.13 m)

3.5 ft. (1066 mm)

10 ft. (3.05 m)

4 ft. (1.2 m)

15 ft. (4.6 m)

H Max. = 15 ft. (4.6 m)

V + H Max. = 40 ft. (12.2 m)

Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
• ALWAYS maintain specified clearances around venting and firestop systems.
• Install wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.

WARNING

Note: Use SLP Series