Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heat & Glo Fireplace HEAT & GLOW XLR-N-AU User Manual

Page 31

Advertising
background image

31

Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. o • 1/13

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

SLP heat shield - designed to be used on a wall 4-3/8 in. (111 mm) to 7-1/2 in. (194 mm) thick.

• If wall thickness is less than 4-3/8 in. (111 mm) the existing heat shields must be field trimmed.

If wall thickness is greater than 7-1/2 in. (194 mm) a DVP-HSM-B will be required.

2-1/2 in. (64 mm)

top clearance

1/2 in. (13 mm)

clearance

bottom & sides

1 in.

(25 mm)

bottom

clearance

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance around

vertical sections

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fire.

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top venting. The center of the hole

is one 10 in. (254 mm) above the center of the horizontal vent pipe.

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials

A*

B

4 ft. (1220 mm)

4 ft. (1200 mm)

A

10 in.

(254 mm)

B

DO NOT PACK WITH

INSULATION OR

OTHER MATERIAL

10 in.

(254 mm)

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield firestop(s). The wall shield

firestop maintains minimum clearances and prevents cold

air infiltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• SLP pipe - A wall shield firestop must be placed on each

side of an interior wall. A minimum 1-1/2 in. (38 mm)

overlap of attached heat shields must be maintained.

• See Section 10.K. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

10 in. (254 mm) greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield firestop is only required on one side and no heat

shield is necessary.