Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. o • 1/13

42

11

Gas Information

A. Gas Pressure Requirements

Pressure requirements for XLR-AU fireplaces are shown

in Table 11.1 below.
Two taps are provided on the right hand side of the gas

control for a test gauge connection to measure the inlet

and outlet pressures.
The fireplace and its individual shut-off valve must be dis-

connected from the gas supply piping system during any

pressure testing of the system at test pressures in excess

of 6 kPa.
If the fireplace must be isolated from the gas supply pip-

ing system by closing an individual shut-off valve, it must

be of the handle-less type.

Incoming gas line should be piped into the valve compart-

ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)

threaded gas inlet connection on the manual shutoff valve.

Table 11.1

B. Gas Connection

Note: Have the gas supply line installed in accordance with

local building codes by a qualified installer approved and/or

licensed as required by the locality.

Note: Before the first firing of the appliance, the gas supply

line should be purged of any trapped air.

Note: Consult local building regulations to properly size the gas

supply line leading to the (Rp 1/2 in.) hook-up at the unit.

WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures

above 6 kPa.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures

equal to or less than 6 kPa.

Figure 11.1. Valve Components

GAS VALVE

CONTROL

MODULE

ON/OFF/REMOTE

SWITCH

DC ADAPTER

Natural Gas

Propane

Butane

Gas Inlet Pressure

1.13 - 3.40 kPa

2.75 - 3.40 kPa

2.75 - 3.40kPa

Outlet (Manifold) Gas Pressure

.80 - .95 kPa

2.36 - 2.61 kPa

2.36 - 2.61 kPa

Gas Rate

.405

m3

/

h

.134

m3

/

h

.111

m3

/

h

Maximum Gas Consumption

26 MJ/h

26.0 MJ/h

22 MJ/h

Burner Injector

DMS 42 (2.350 mm)

DMS .057 (1.450 mm)

DMS 55 (1.325)

Pilot Injector

51

30

30

Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum

inlet pressure of

3.40 kPa. For pressures over 3.40 kPa, an in line pressure regulator must be installed

upstream from the gas control valve.

Leak test all gas line points and the gas control valve prior

to and after starting the gas appliance.

IMPORTANT NOTICE:

(Items 1, 2 and 3 applies to

ALL Heat & Glo gas appliances)
1. 1/2 in. GAS LINE: Run through cavity 70 mm

above finished hearth level,

NOT RIGID, NOT

CLIPPED, with minimum 500 mm into cavity and

120 mm back from plaster face.

2. PVC (COMPOSITE) GASLINE must terminate

minimum 500 mm short of gas heater. Copper pipe

MUST be the final connection to the gas heater.

3. ISOLATING SWITCH: Location within 1 metre

of fireplace, subject to mantelpiece etc. Check to

ensure it remains clear of any mantelpiece instal-

lation.