Top vent - horizontal termination - (continued) – Heat & Glo Fireplace HEAT & GLO SLR-B (COSMO) User Manual

Page 27

Advertising
background image

Heat & Glo • SLR-B • 2195-900 Rev. P • 12/11

27

H

2

H

1

V

2

V

1

Top Vent - Horizontal Termination

Venting with 3 elbows

Note: Use SLP Series

components only.

1. Top Vent - Horizontal Termination - (continued)

Figure 7.6

SLR-B

V

1

Minimum

H

1

+ H

2

Maximum

V

2

V

1

+ V

2

Minimum

90° Elbow

6 ft.

1.8 m

*

*

1 ft.

305 mm

10 ft.

3.0 m

*

*

2 ft.

610 mm

12 ft.

3.7 m

*

*

3 ft.

914 mm

14 ft.

4.3 m

*

*

H

1

+ H

2

MAX. =14 ft. (4.3 m)

V

1

+ V

2

+ H

1

+ H

2

MAX. = 40 ft. (12.2 m)

*No specifi c restrictions on this value EXCEPT V

1

+ V

2

+ H cannot exceed 40 ft. (12.2 m)

Note: There MUST be a 25%

reduction in total H when using

fl ex vent except when using the

simple up and out installation

(see Figure 7.3).

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS

termination caps are not approved for use with pro-

pane (LP) fuel. May lead to elevated glass temper-

ature that may cause tempered glass breakage.