Heat & Glo Fireplace HEAT & GLO SLR-B (COSMO) User Manual

Page 41

Advertising
background image

Heat & Glo • SLR-B • 2195-900 Rev. P • 12/11

41

C. Secure The Vent Sections

• Vertical runs of pipe must be supported every 8 ft. (2.44 m).
• Horizontal sections must be supported every 5 feet

(1.52 m).

• Vent supports or plumbers strap (spaced 120º apart)

may be used to support. See fi gures 10.5 and 10.6.

• Wall shield fi restops may be used to provide horizontal

support.

• Ceiling fi restops have tabs that may be used to provide

vertical support.

WARNING! Risk of Fire, Explosion or Asphyxiation!

Improper support may allow vent to sag and separate.

Use vent run supports and connect vent sections per in-

stallation instructions.

DO NOT allow vent to sag below

connection point to appliance.

Figure 10.5 Securing Vertical Pipe Sections

Figure 10.6 Securing Horizontal Pipe Sections

B. Assemble Slip Sections

• Slide the inner fl ue of the slip section into the inner fl ue of

the pipe section and the outer fl ue of the slip section over

the outer fl ue of the pipe section. See Figure 10.3.

• Slide together to the desired length.

Figure 10.3 Slip Section Pilot Holes

Figure 10.4 Screws into Slip Section

Pilot hole

• Continue adding pipe as necessary following instructions

in “Assembling Pipe Sections.”

NOTICE: If slip section is too long, the inner and outer fl ues

of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC

termination cap, all pipe system joints shall be sealed using

a silicone sealant with a minimum of 300ºF continuous

exposure rating.
• Apply a bead of silicone sealant inside the female outer

pipe joint prior to joining sections.

• Only outer pipes are sealed, sealing the inner fl ue is not

required.

• All unit collar, pipe, slip section, elbow and cap outer

fl ues shall be sealed.

• Maintain a 1-1/2 in. (38 mm) overlap between the slip

section and the pipe section.

• Secure the pipe and slip section with two screws no

longer than 1/2 in. (13 mm), using the pilot holes in the

slip section. See Figure 10.4.