C. Install the Ceiling Firestop

A ceiling fi restop

MUST be used between

fl oors and attics.

SLP pipe only - Frame opening 9 in. x

9 in. (229 mm x 229 mm) whenever the

vent penetrates a ceiling/floor (see Figure

8.4).

• Frame the area with the same sized lumber

as used in ceiling/fl oor joist.

• The ceiling fi restop may be installed above or

below the ceiling joists when installed with a

attic insulation shield. It must be under joists

between fl oors that are not insulated. Refer

to Figure 8.5.

• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-

lation around the vent. Insulation must be kept

back from the pipe to prevent overheating.

Figure 8.4 Installing Ceiling Firestop

ATTIC ABOVE

A

PIPE
SLP

A

9 in. (229 mm)

A

Figure 8.5 Installing the Attic Shield

3 FASTENERS

PER SIDE

INSTALL ATTIC INSULATION SHIELDS

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

CEILING FIRESTOP

INSTALLED BELOW CEILING

CEILING FIRESTOP

INSTALLED ABOVE CEILING