Heat & Glo • SLR-B • 2195-900 Rev. P • 12/11

29

Figure 7.8 Vertical Vent Maximum

Note: If installing a vertical vent/termination off the top of the

appliance, the optional exhaust restrictor may be needed.

V

1

V

1

= 44 ft. Max. (13.4 m)

Top Vent - Vertical Termination

No Elbows

Note: Use SLP Series

components only.

Exhaust restrictor Instructions
1. Locate the two pilot holes located in the inside fi rebox

heat shield as shown in Figure 7.9.

2. Center the exhaust restrictor such that the through

holes in the vent restrictor align with the pilot holes in

the restrictor.

3. Use two 1/2 in. self-piercing screws to secure vent

restrictor to fi rebox heat shield. See Figure 7.10.

Exhaust restrictors are recommended for these vertically

terminated products which have excessive draft. Exhaust

restrictors will compensate for high draft, and restore vi-

sual fl ame height. If the vent confi guration has a total ver-

tical of 15-44 feet, an exhaust restrictor may be needed.

The exhaust restrictor can be located in the appliance

manual bag.

Figure 7.10 Exhaust Restrictor Installation

Figure 7.9 Location of Pilot Holes

PILOT HOLES

NOTICE: Before painting, contact your dealer for

information on the appropriate high temperature paint.

4. In some applications, such as those where the fi re-

place is elevated off the fl oor, the vent restrictor may

be painted, but painting is not required.