CHAPTER4 SETTING

10

4.2 Parameter setting of the Inverter

Following table describes setting items relate SJ200-2/L200-2 series Inverter with connecting SJ2-CO.

Following parameter will appear with connecting SJ2-CO to SJ200-2/L200-2 Inverter.

Parameter

Function

Range of DATA

Initial

DATA

Note

P044

Timer setting of
Communication

timeout Whilst

running

0.00~99.99

0.00

**

P045

Inverter action

when

communication

error

00(TRIP) / 01(TRIP after

deceleration stop)

/ 02(ignore) / 03(Free-RUN)

/ 04(deceleration stop)

01

It is effective when

“Object #6007”

setting is ‘-3’.

P049*

Motor Poles

setting for

revolution per

minutes

0 to 38

(It is possible to set only even

number )

Setting value ‘0’, monitoring unit is

Hz.

Setting value except ‘0’, monitoring

unit is min

-1

.

0

Note*: As “P049 Command” value is setting ‘0’, unit of “Index 6042,6043,6044,6046,6048-1,6049-1”

is ‘Hz’.

Note**: CANopen Interface Option cannot detect bus-off status with heartbeat. Using P045 command,

set value of P044 instead of detecting bus-off status.

4.3 Power Supply LED check

If the Power Supply LED(See 1.3) is not ON ,please remount(See 2.1) the SJ2-CO unit again.