CHAPTER5 CANOPEN COMMUNICATION FUNCTION

14

5.1.6 Control word (Index: 6040h)

The control word is used to send control commands to the inverter. (HOST-> Inverter)

Bit

Description

Note

0

Switch On-Stop

Mandatory

1

Disable Voltage-Free Run Stop

Mandatory

2

Quick stop-Stop using 2CH setting

Mandatory

3

Enable Operation-Run

Mandatory

4

RFG Enable

Mode Specific

5

RFG Unlock

Mode Specific

6

RFG Usr ref

Mode Specific

7

Reset Fault (raising edge)

Mandatory

8

Halt

Mode Specific

9

(Undefined)

Reserved

10

(Undefined)

Reserved

11

RDY Function Enable

Manufacturer Specific

12

NetRef

Manufacturer Specific

13

NetCtrl

Manufacturer Specific

14

Move forward

Manufacturer Specific

15

Move reverse

Manufacturer Specific

To use setting frequency from CANopen, please set bit NetRef(bit 12). An inverter parameter A001

is set 10(Calculate function output) with setting NetRef bit is 1, Calculate function output will not

work.

To handle RUN/STOP command form CANopen, you have to set a bit NetCtrl.