CHAPTER6 COUNTERMEASURE FOR ABNORMALITY

22

6.4 LED display and Countermeasure

Following states are indicated by Module LED and CANopen status LED.
MOD (Module status) LED: It indicates Inverter condition.
CAN (CANopen status) LED: it indicates CANopen status.

LED

Color

State

Countermeasure

Category

Green ON

The inverter is in Normal
condition.

-

Mandatory

Green
single flash

The inverter is in Stand-by
condition.

-

Mandatory

Red ON

An

abnormality

occurred

which is impossible to restore.

Need to fix the inverter.

Mandatory

Red single
flash

An

abnormality

occurred

which is possible to restore.
Mostly this state occurs, when
the inverter is in trip condition.
But except status below.
User initializing with b084 set
to 01 or 02.

When in trip, remove the trip
causes.
When initializing, the inverter
starts up automatically the
BOOTUP process after the
initializing.

Mandatory

MOD

OFF

Power off

-

Mandatory

Green ON

OPERATIONAL

-

Mandatory

Green
single flash

STOPPED

-

Mandatory

Green
Blinking

PRE-OPERATINAL

-

Mandatory

OFF

no error

-

Mandatory

Red single
flash

Warning limit reached

Any Flaming error

Mandatory

CAN

Red double
flash

Error Control Event

The Guarding Protocol or the
Heartbeat

Protocol

is

processing.

Mandatory

notes

LED ON:

constantly on

LED OFF:

constantly off

LED blinking:

iso-phase on and off with a frequency of approximately 2.5Hz:

on for approximately 200ms and off for approximately 200ms.

LED single flash:

one short flash (approximately 200ms) followed by a long off phase (approximately 1000ms).

LED double flash:

a sequence of two short flashes (approximately 200ms),

separated by an off phase (approximately 200ms).

The sequence is finished by a long off phase (approximately 1000ms).